Impress case Study

Oil prices dropped by an average of 9.5% in 08/09 compared to the previous winter period 07/08. This will enhance the actual savings.

The mean temperature for East Anglia during winter 07/08 was 5.7°c. The mean temperature for East Anglia during winter 08/09 was much cooler at 3.4°c.

The heating system thermostats are set to 16°, resulting in an increase in the requirement for heating in East Anglia of 22%.

This analysis excludes the purchase and installalation costs of £21,268 in the first year.

Winter 07/08 (pre-fans) total oil usage =£138,337

Winter 08/09 (post-fans) total oil usage = £83,837

Oil use reduction & savings, winter 08/09 = £54,500

Restated savings, inc lower Oil price 08/09 = £49,322

Restated Oil use & savings, inc lower temp 08/09 = £63,144

Airius System running costs per winter season= £793

First Winter Savings = £62,351

Key Points:


  • 45.07% - Overall Savings 08/09

  • £62,351 - first winter savings

  • £21,268 - full system & installation cost

  • 3,000m² - floor area

  • 5.7˚C - mean temp 07/08

  • 3.4˚C - mean temp 08/09

  • £793 - Airius running costs per winter season

  • Installed into Can Assembly area

  • System - 34 units

  • Part of the Ardagh Group





“Overall savings taking into account lower temperatures and prices in winter 08/09 = 45.07% The full cost of the Airius units is re-couped within a matter of months - first winter savings of £62,351 measured against a total spend of £21,268.” - Paul Matten (Plant Engineer)